GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance, refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. A copy of the integrity test report described herein in accordance with ASTM D5957 shall be provided to the
Building Official for review at time of final inspection.
3. Contractor shall submit to the Building Official for review the system specifications and details. Submission of
these documents, as well as the proper application and installation of all materials shall be the sole responsibility
of the contractor.
4. Flashings shall be installed according to the manufacturers published standard details, specific details, approved
by Polycoat Products and shall be submitted to the Building Official for review.
5. All work shall be performed by a Contractor licensed to do roofing/ waterproofing and be a Manufacturer
Trained 'Qualified Applicator' approved and licensed by Polycoat Products. Polycoat Products shall supply a list
of approved applicators to the authority having jurisdiction.
6. All attachment and sizing of perimeter nailers, metal profile, and/or flashing termination designs shall conform
with Roofing Application Standard RAS 111 and the wind load requirements of applicable Building Code.
7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these areas. Fastener
densities shall be increased for both insulation and base sheet as calculated in compliance with Roofing
Application Standard RAS 117. Calculations prepared, signed and sealed by a Florida registered Professional
Engineer, Registered Architect, or Registered Roof Consultant (When this limitation is specifically referred
within this NOA, General Limitation #9 will not be applicable.)
8. A non-skid surfacing is required for all pedestrian areas, plaza decks or balconies.
9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones (i.e. field,
perimeters, and corners). Neither rational analysis, nor extrapolation shall be permitted for enhanced fastening at
enhanced pressure zones (i.e. perimeters, extended corners and corners). (When this limitation is specifically
referred within this NOA, General Limitation #7 will not be applicable.)
10. Aquaseal 5000WC/GC, T-Shield WC/GC, PC-IM 129 or B-Tuff 921 shall not be installed over lightweight
insulating concrete.
11. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61G20-3 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No.: 23-0623.02
Expiration Date: 01/25/29
Approval Date: 01/25/24
Page 5 of 5