CLIENT: POLYCOAT PRODUCTS
Report No: RJ4296-1
October 13, 2015
Page 2 of 3
PREPARATION: The sample material was submitted in three pieces 22” wide by 8’ feet long conforming to
test chamber dimensions.
CONDITIONING: The test specimen was conditioned to a constant weight at a temperature of 73.4 ± 5º F (23
± 2.8º C) and a relative humidity of 50 ± 5 %.
CEMENT BOARD PLACEMENT: The 1/4” cement boards were placed between the test specimen and the
chamber lid.
E 84 TEST DATA SHEET:
CLIENT: Polycoat Products DATE: 10/13//2015
SAMPLE: Polyeuro MH 751FR Coating.
IGNITION: 27 seconds.
FLAME FRONT: 6 feet maximum.
TIME TO MAXIMUM SPREAD: 3 minutes, 53 seconds.
TEST DURATION: 10 minutes.
CALCULATION: 53.18 X .515 = 27.39
SUMMARY: FLAME SPREAD: 25 SMOKE DEVELOPED: 250 (257.67)
SUMMARY OF ASTM E84 RESULTS: Because of the possible variations in reproducibility, the results are
adjusted to the nearest figure divisible by 5. Smoke Density values over 200 are rounded to the nearest figure
divisible by 50.
In order to obtain the Flame Spread Classification, the above results should be compared to the following
table:
NFPA CLASS IBC CLASS FLAME SPREAD SMOKE DEVELOPED
A A 0 through 25 Less than or equal to 450
B B 26 through 75 Less than or equal to 450
C C 76 through 200 Less than or equal to 450
BUILDING CODES CITED:
1. National Fire Protection Association, ANSI/NFPA No. 101, "Life Safety Code".
2. International Building Code, Chapter 8, Interior Finishes, Section 803.
THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS
NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED.
THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED.